Remote unit for OF cable supervision
Remote monitoring of oil pressure in oil-filled underground cables.
Oil-filled underground cables depend on pressure staying within range: an undetected leak degrades the insulation and can end in a costly failure. This remote unit is built on the same platform as the Telemetry RTU for MV substations and adds analog acquisition modules to read pressure transmitters, scaling from 4 to 32 sensors with no hardware change. It reports a drop as it happens, over the same protocol your SCADA already speaks.
-
Scalable
From 4 to 32 sensors by adding analog acquisition modules to the RS-485 bus, with no change of unit or platform.
-
Redundant
Cellular link with automatic fallback and UPS supply: events survive a network or power outage.
-
Compatible
Native DNP3.0 and MODBUS: it joins the existing SCADA with no intermediate development.
-
Early detection
A pressure drop is reported as it happens, before it degrades the insulation.
01Technical specifications
Technical specifications
-
Inputs and outputs
- 8 dry-contact digital inputs, 3.5 kV isolation, up to 50 VDC (220 VDC on request)
- 8 dry-contact relay digital outputs, 100 V / 0.4 A
- 4 built-in analog inputs (4-20 mA or 0-5 VDC)
- Expansion up to 32 pressure sensors by adding analog acquisition modules (3 channels each) over the RS-485 bus
- Pressure sensor supplied: PI transmitter 0-4 Bar, AISI 316 body, 1/4" NPT connection
- Sensor: -40°C to 105°C temperature range, 8-30 VDC power, 2-wire 4-20 mA output
-
Connectivity and communications
- 2 RS232 ports
- 1 RS485 port (expansion bus for analog acquisition modules)
- 1 10/100 Mbps Ethernet port
- LTE cellular connectivity with automatic 3G/2G fallback, dual SIM
- Optional multi-constellation GPS
-
Protocols and gateway
- DNP3.0, IEC 60870-5-104 and MODBUS TCP as a slave toward the SCADA
- MODBUS TCP, RTU and ASCII as a master toward the analog acquisition modules and other field devices
- Protocol gateway: concentrates and converts MODBUS to DNP3.0 or IEC 104
- Transparent TCP bridges for each serial port
-
Management and reliability
- Local and remote configuration via web interface
- Remote (OTA) or local USB firmware update
- Integrated battery charger with automatic weekly test
- 72-hour battery autonomy on power loss
- Automatic alarm on battery failure, reported to the SCADA
- IP65 enclosure, operating temperature -40°C to +85°C
02Main applications
Main applications
- Pressure monitoring on oil-filled cables
- Complex underground networks
- High and medium voltage substations
- Integration with existing SCADA systems
- Predictive maintenance of critical assets
- Expanding measurement points without replacing the existing RTU